SDG Electronics

AC power and power factor

Single-phase sinusoidal RMS power triangle and optional displacement-power-factor correction.

Development preview. Check the assumptions below before relying on a result. Calculations run in your browser.

Loading calculator…

How it calculates

Model: S=Vrms Irms; P=S cosφ; Q=S sinφ; Qc=P(tanφinitial−tanφtarget); C=Qc/(2πf Vrms²).

Assumptions

  • Single-phase sinusoidal voltage and current only. Displacement PF is not true PF for distorted waveforms; harmonics, resonance, inrush and capacitor switching are outside this model.
  • Capacitor result corrects a lagging load toward the target. Existing leading loads or already-better PF return zero added capacitance.

Worked example

These are the calculator's default inputs. Change any input above to recalculate.

Inputs

Phase input
power factor
RMS voltage
230 V
RMS current
5 A
Displacement power factor
0.8
Signed phase angle (+lagging)
36.8699 degree
PF mode reactive sign
lagging
AC frequency
50 Hz
Target lagging PF for capacitor sizing
0.95

Results

Real power
920 W
Reactive power (+inductive)
690 var
Apparent power
1150 VA
Displacement PF
0.8
Current lag angle
36.8699 degree
Required capacitive compensation
387.611 var
Parallel correction capacitance
0.0000233233 F

All electronics calculators